Short-Circuit / Fault Current in Network Users’ Premises
Prospective short-circuit/fault current and external source impedance at the output point of the EAC's meter.
Translation:
The 16th Edition Regulations of the United Kingdom’s Institution of Engineering and Technology for electrical installations require that, in the event of a short circuit/earth fault, every protective device installed in the electrical installation satisfies the following criteria:
a) Its breaking capacity must not be lower than the prospective fault current.
b) Its operating time and fault isolation time must be within the limits specified by the Regulations.
In order to make it possible to determine both the breaking capacity and the operating time of a protective device, it is necessary for the designer of the electrical installation to know the fault current at the point where the device will be installed.
The Electricity Authority of Cyprus has examined typical supply cases and, for each case, has calculated the short-circuit level and the earth fault current, as well as the external fault source impedance at the meter output point (the origin of the installation).
The results of the above calculations, upon request, should be made available to designers, who bear the ultimate responsibility for calculating the short-circuit/earth fault current at all installation points of the protective devices.
Electricity supplies to consumers’ premises are provided either through overhead lines or through underground cables. In both methods, depending on the magnitude of the supplied load and the distance from the Electricity Authority of Cyprus network, conductors of various cross-sections and lengths are used, resulting in variations in the short-circuit/earth fault current.
For the purpose of calculating the maximum short-circuit/earth fault current, the Electricity Authority of Cyprus assumed that the installation would ultimately be supplied through the largest transformer it may install (1000 kVA) and carried out calculations for various distances between the transformer and the installation, as well as for various supply conductor cross-sections, so as to cover all typical supply cases.
3.1 Three-Phase Supply from a 1000 kVA Power Transformer
The prospective short-circuit current Ip at the Substation Distribution Board is 25 kA and the external source impedance is Zp = 10.2 mΩ.
The prospective asymmetrical Phase-Neutral short-circuit current at the Substation Distribution Board Ipn is 24.9 kA and the external source impedance is Zpn = 9.7 mΩ.
The prospective symmetrical short-circuit current Ip and the external source impedance Zp in the event of a Phase-Phase-Phase-Neutral short circuit, as well as the prospective asymmetrical short-circuit current Ipn and the external source impedance Zpn in the event of an asymmetrical Phase-Neutral fault, have been calculated for distances from 5 m up to 75 m from the Substation Distribution Board for the following four different supply cases:
3.1.1 Cable 3 × 300/110 mm² Al.
For the results, see TABLE 1.
3.1.2 Cable 3 × 185/90 mm² Al.
For the results, see TABLE 2.
3.1.3 Cable 3 × 70/35 mm² Al.
For the results, see TABLE 3.
3.1.4 Cable 3 × 35/25 mm² Al.
For the results, see TABLE 4.
Note: In the TN-C-S earthing system of the installation, Zpn = Ze.
3.2 Single-Phase Supply from a 1000 kVA Power Transformer
The prospective short-circuit current (Ipn) and the external source impedance (Zpn) at the Substation Distribution Board are as follows:
Ipn = 16.0 kA
Zpn = 15.2 mΩ
The attached TABLE 5 presents both the prospective short-circuit current (Ipn) and the external source impedance (Zpn) for distances from 0 m up to 20 m for the case of using a 35 mm² Al supply cable.
The maximum source impedance value that may occur at a customer connection point on the Electricity Authority of Cyprus low-voltage network is 0.35 Ω.
Note: In the TN-C-S earthing system, Zpn = Ze.
The prospective short-circuit current Ip at the Substation Distribution Board is 50 kA and the source impedance Zp is 0.005 Ω with a fault angle of 59.53° (R = 0.0012 Ω, X = 0.0048 Ω).
The prospective short-circuit current Ip at the Substation Distribution Board is 36 kA and the source impedance Zp is 0.0069 Ω with a fault angle of 77.3° (R = 0.0015 Ω, X = 0.0068 Ω).
All data and information referred to in this Directive regarding the prospective short-circuit and earth fault current, as well as the external source impedance at the origin of the electrical installation, can also be found on the website of the Electricity Authority of Cyprus.
In the event that a designer does not have the required information in order to classify the electrical installation being designed into the correct supply category, they should contact the relevant Regional Office of the Electricity Authority of Cyprus, which will provide guidance regarding the supply category applicable to the case under study.